A Three-Level Hysteresis Function Approach to the Sliding-Mode Control of Single-Phase UPS Inverters
Kukrer, O.; Komurcugil, H.; Doganalp, A.
Industrial Electronics, IEEE Transactions on
Volume 56, Issue 9, Sept. 2009 Page(s):3477 - 3486
Digital Object Identifier 10.1109/TIE.2009.2016512
Summary:A new approach to the sliding-mode control of single-phase uninterruptible-power-supply inverters is introduced in continuous time. A three-level hysteresis sliding function is used to directly control the inverter switches, with the result that a transistor is switched during a half-cycle while it remains either on or off during the other cycle. An expression is derived for the predicted switching frequency. The performance of the proposed control method has been tested through computer simulations and experiments under different loads (a resistive load and a diode bridge rectifier load). Simulation and experimental results verify the correct operation of the proposed control strategy. In addition, the switching frequency prediction is seen to be quite accurate.
View citation and abstract |