Wireless-Control Strategy for Parallel Operation of Distributed-Generation Inverters
Guerrero, J.M.; Matas, J.; de Vicuna, L.G.; Castilla, M.; Miret, J.
Industrial Electronics, IEEE Transactions on
Volume 53, Issue 5, Oct. 2006 Page(s):1461 - 1470
Digital Object Identifier 10.1109/TIE.2006.882015
Summary:In this paper, a method for the parallel operation of inverters in an ac-distributed system is proposed. This paper explores the control of active and reactive power flow through the analysis of the output impedance of the inverters and its impact on the power sharing. As a result, adaptive virtual output impedance is proposed in order to achieve a proper reactive power sharing, regardless of the line-impedance unbalances. A soft-start operation is also included, avoiding the initial current peak, which results in a seamless hot-swap operation. Active power sharing is achieved by adjusting the frequency in load transient situations only, owing to which the proposed method obtains a constant steady-state frequency and amplitude. As opposed to the conventional droop method, the transient response can be modified by acting on the main control parameters. Linear and nonlinear loads can be properly shared due to the addition of a current harmonic loop in the control strategy. Experimental results are presented from a two-6-kVA parallel-connected inverter system, showing the feasibility of the proposed approach
View citation and abstract |